The NEC® guides an electrician through the main components of the calculation, thus providing all the information that is necessary for a motor installation.

Correct Answer

verifed

verified

The work of the modern electrician requires a knowledge of National Electrical Code® requirements that govern three-phase motor installations and the ability to apply these requirements to installations.

Correct Answer

verifed

verified

True

Wire types and sizes are selected by the ambient temperatures of the place of installation and the economics of the total installation, such as the minimum size of conduits, cost of the wire sizes, and labor cost for installing the various selections.

Correct Answer

verifed

verified

True

In a three-phase motor installation, what are three specific facts that must be determined for each of the three branch circuits constituting the load of the installation?

Correct Answer

verifed

verified

The three specific facts that must be de...

View Answer

NEC® Article 430.52 Exception 1 states that if the values for branch-circuit protective devices as determined using the percentages in Table 430.52 do not correspond to the standard device sizes or ratings, then the nearest smaller size rating or setting should be used.

Correct Answer

verifed

verified

When the conductors of a feeder supply two or more motors, the required wire size is determined using Code rules.

Correct Answer

verifed

verified

The branch-circuit, short-circuit protection of a wound-rotor induction motor is required by Table 430.52 of the Code not to exceed 150% of the ____________________ running current of the motor.

Correct Answer

verifed

verified

The term ____________________ is synonymous with ampere capacity.

Correct Answer

verifed

verified

List two of the many facets to the correct installation of a motor.

Correct Answer

verifed

verified

There are many facets to the correct installation, including: • feeder and feeder protection • branch-circuit and branch protection • conductor sizes and overcurrent protection • running overcurrent protection • secondary circuit protection

NEC 430.32(E) states that the secondary circuits of wound-rotor induction motors, including the conductors, controllers, and resistors, shall be considered as protected against overload by the motor running overcurrent protection in the ____________________ circuits.

Correct Answer

verifed

verified

Showing 1 - 10 of 10